The induction motor in depth
Equivalent circuit, where the power goes, the torque-speed curve point by point, starting current and what voltage and rotor resistance change.
35 min
On this page
Lesson A4 introduced the induction motor. This lesson turns it into numbers you can use to choose one. All the figures below come from the same example motor as Lab I: 230 V per phase, Ω, Ω, Ω, four poles, 50 Hz.
The equivalent circuit
Per phase, the motor behaves like a transformer whose secondary load is the resistance . Neglecting the magnetising branch, the rotor current is
The resistance is the clever part: it is large when the slip is small, so a lightly loaded motor draws little current, and it falls to at standstill, so a starting motor draws a lot.
FoundationStart here if this is new to you
You do not have to love circuits to use this. Remember one thing: the motor looks like a resistance that gets smaller as the motor slows down. Smaller resistance, bigger current, bigger torque, until the motor slows too much and the curve turns over.
Where the power goes
The power that crosses the air gap to the rotor, , splits in a fixed way:
For the example motor carrying 80 N·m, the slip is 3.56 %. Then kW, of which 447 W heats the rotor bars and 12.12 kW reaches the shaft (less friction and windage). Add the stator copper and iron losses and a motor of this size is typically 88 to 92 % efficient.
The torque-speed curve
Torque follows from the circuit:
- Starting torque
- 84.0 N·m
- Breakdown torque
- 197.2 N·m
- Breakdown slip
- 0.194
- Operating speed
- 1,447 rpm
- Operating slip
- 3.56 %
Three points of that curve matter when you choose a motor:
| Point | Where | Example motor | Why it matters |
|---|---|---|---|
| Starting (locked-rotor) torque | 84 N·m | must beat the load's breakaway torque | |
| Breakdown (pull-out) torque | 197 N·m | the largest load peak it can carry | |
| Rated point | –5 % | rated torque | continuous, thermally allowed |
Catalogues give the first two as a percentage of rated torque, for example " 220 %, 300 %".
Predict first
The supply voltage sags to 90 %. By how much does the motor's torque at a given slip fall?
Starting current
At standstill the impedance is at its smallest. The example motor draws
against 19.3 A at its 80 N·m operating point: 5.4 times more. Real motors draw 5 to 8 times their rated current when started direct-on-line. The supply, the cables and the protection must survive it, and it causes a voltage dip for everyone else on the line. Chapter 2 compares the ways of reducing it.
Changing the curve
- Voltage scales the whole curve by and leaves the breakdown slip where it is.
- Rotor resistance moves the breakdown point to a higher slip without changing its height. A wound-rotor motor uses external resistors to start with high torque and low current, then shorts them.
- Rotor bar design does the same in a cage motor: deep or double-cage bars have a high resistance at standstill (current crowds to the surface) and a low one when running. IEC 60034-12 groups cage motors into designs such as N (normal starting torque) and H (high starting torque).
- Frequency moves the synchronous speed. With V/f kept constant, the curve slides along the speed axis with almost the same shape: that is how a VFD controls speed (lesson A5, Chapter 2).
ExplorerGo deeper: derivations and open questions
Kloss's formula. Neglect and the curve becomes
With only two catalogue numbers, the breakdown torque and its slip, you can sketch the whole curve. How far is it from the exact curve of the example motor at ? Where does the error come from?
Magnetising current. The circuit above neglects the magnetising branch . Put it back and the no-load current is no longer zero: typically 25 to 50 % of rated current, almost all reactive. How does that explain the poor power factor of a lightly loaded motor?